18
Potable Water and Space Heating
1. All piping materials and components connected to
the water heater for the space heating application
shall be suitable for use with potable water.
2. Toxic chemicals, such as used for boiler treatment,
shall not be introduced into the potable water used
for space heating.
3. If the heater will be used to supply potable water,
it shall not be connected to any heating system or
components previously used with a non-potable
water heating appliance.
4. When the system requires water for space heating
at temperatures higher than 140°F, a means such
as a mixing valve shall be installed to temper the
water in order to reduce scald hazard potential.
CAUTION: When this heater is used for both
potable water and space heating, observe the
following to ensure proper operation.
Fig. 13: Single Domestic Hot Water Heater and Storage
Tank
Soft (0-4 grains per gallon) Medium (5-15 grains per gallon) Hard* (16-25 grains per gallon)
Model
No.
T
gpm
P
MTS SHL
T
gpm
P
MTS SHL
T
gpm
P
MTS SHL
992B 28 60 2.7 2 4.6 20 83 5.2 2 8.6 13 132 13.1 2 21.0
1262B 30 72 4.4 2 7.0 20 106 9.6 2 14.8 16 132 14.8 2 22.7
1532B 30 86 7.1 2 10.7 20 132 16.5 2 24.4 20 132 16.5 2 24.4
1802B 30 101 10.7 2 15.5 23 132 18.3 2 26.1 23 132 18.3 2 26.1
2002B 30 112 13.9 2 19.7 26 132 19.0 2 26.9 26 132 19.0 2 26.9
2072B 30 116 14.8 2 21.0 27 132 19.0 2 26.9 27 132 19.0 2 26.9
2342B 30 132 21.4 2 29.3 30 132 21.4 2 29.3 30 132 21.4 2 29.3
Table H: Domestic Water Heater Flow Rate Requirements
Pool Heating
The Hi Delta pool heater is equipped with an external
pump and bypass arrangement as standard equip-
ment. This arrangement blends outlet water with the
inlet water to increase the inlet water temperature,
thereby reducing the likelihood of condensation form-
ing on the heat exchanger. The pump also serves to
CAUTION: Power to the heater should be
interlocked with the main system pump to make sure
the heater does not fire without the main system
pump in operation. Improper flow control can
damage the heater. Uncontrolled flow (too high) or
restricted flow (too low) can seriously damage the
heater. Follow these instructions to make sure your
heater is properly installed.
ΔT = Temperature rise, °F
ΔP = Pressure drop through heat exchanger, ft
SHL = System head loss, ft (based on heater and tank placed no more than 5 ft apart and equivalent length pipe/fittings of 2
1
⁄2”
tube = 25 ft)
gpm = Gallons per minute, flow rate
MTS = Minimum tubing size
*Must utilize optional cupro-nickel tubes. If over 25 grains per gallon, a water softener/treatment system must be utilized.
Caution: For scale free operation with "Hard Water" (16-25 grains per gallon of total hardness), the operating control must NOT be
set higher than 130 F. For higher than 130 F operation, a water softener/treatment system must be utilized.