8
MOUNTING
On vertical vents, the vent damper may be mounted with the actuator in any position. On horizontal vents,
do not mount the actuator either directly above or directly below the vent pipe; mount the vent damper actuator
to the side of the vent.
The vent damper is set up for a continuous pilot system. If the vent damper is installed on an Intermittent Pilot
or Hot Surface Ignition equipped system, the energy savings of the vent damper can be improved by plugging the
hole in the vent damper blade using the knockout plug, Part No. 105612R, provided in the parts envelope.
Hole in Vent Damper Blade
Closed Position
Fig. #8994
DO NOT plug the hole if installing the vent damper on a continuous pilot system as this will create a
hazardous condition.
Fig. #8183.0
INSTALLING THE VENT DAMPER IN HORIZONTAL
& VERTICAL VENTS.
Fig. #152323
D80D GENERAL WIRING DIAGRAM
INSTALL THE VENT DAMPER TO SERVICE ONLY THE SINGLE APPLIANCE FOR WHICH IT IS INTENDED.
IF IMPROPERLY INSTALLED, A HAZARDOUS CONDITION, SUCH AS AN EXPLOSION OR CARBON
MONOXIDE POISONING, COULD RESULT.
1K
1K1
1K2
D80
MOTOR
N.C.
END
SWITCH
N.O.
1K3
C.
4
32
1
YELLOW
BLUE
BLACK
ORANGE
CABLE
NO
YES
NO
YES
INSTALL VENT
DAMPER WITH
ACTUATOR TO SIDES
OF VENT ONLY. DO
NOT MOUNT ABOVE OR
BELOW VENT.
TO CHIMNEY
TO BOILER VENT DAMPER
FLOW >
HORIZONTAL INSTALLATION
TO CHIMNEY
AT BOILER
DRAFT
HOOD
VENT
DAMPER
VERTICAL
INSTALLATION
ACTUATOR MAY BE
INSTALLED IN ANY
POSITION ON VERTICAL
PIPE.