Castile Pellet Insert
NOTE: Check
clearances carefully for this type of instal-
lation to ensure adequate room for outside air venting.
Check building codes prior to installation.
Installation MUST comply with local, regional, state and
national codes and regulations.
Consult local building, fi re offi cials or authorities having
jurisdiction about restrictions, installation inspection, and
permits.
CAUTION
NOTE: In Canada only a full reline is allowed per ULC
S628, ORD ULC C1482-M1990.
B. Full Reline W
ith Outside Air - Vertical
Figure 16.1
Outside Air
Termination
at
Chimney Top
(Vertical)
305mm min.
below
305mm min.
above
NOTE; Use metal plate around
exhaust vent pipe and seal all
edges with non-flammable insula-
tion such as fiberglass, mineral
wool or ceramic.
Do not use high temperature caulk-
ing materials to seal any edge to
prevent furture serviceability.
NOTE: In Canada this fi replace insert must be installed
with
a continous chimney liner a 6 inch (152mm) in diam-
eter extending from the fi replace insert to the top of the
chimney. The chimney liner must conform to the Class
3 requirments of CAN/ULC-S635, Standard for Lining
Systems for Extising Masonry or Factory-Built Chimneys
and Vents, or CAN/ULC-S640, Standard for Lining Sys-
tems for New Masonry Chimneys.