Baxi Potterton WH65 Boiler User Manual


 
15
INSTRUCTIONS PERTAINING TO THE INSTALLER 926.772.1 - GB/IE
12.2 VERTICAL FLUE TERMINAL
Ø 80/125 mm
INSTALLATION OPTIONS
This type of installation can be carried out both on a at or pitched roof by tting a terminal, an appropriate
weathering tile and sleeve, (supplementary ttings supplied as options).
L max = 10 m
L max = 10 m L max = 9 mL max = 8 m
0310_0107
L = refer also the table
12.1 HORIZONTAL FLUE TERMINAL
Ø 80/125
INSTALLATION OPTIONS
0602_0702
L = refer to table
To ensure the correct rated heat output to the maximum and minimum heat input, it is necessary to update
the speed (rpm) of the fan, it depends on the length of the ue (par. 12), in accordance with the installation of
ue and air pipes as indicated in the tables below. The factory-set value is referred to the minimum length of
ue pipe (0÷4 m for concentric, 0÷20 m for twin). To carry such updating, changing the speed of the fan (rpm)
at the maximum and minimum heat input, refer to par. 16.
12.5 FAN RPM UPDATING DEPENDING ON FLUE LENGTH (e.g. figure 7)
(*) Default setting parameters
CONCENTRIC PIPE Ø 80/125
(C13-C33-C43)
Pipes length (m)
Parametres
H536-H613
Parametres
H612
Max heat output (rpm) Min heat output (rpm)
(*) 0 - 4
5500 1900
5 - 10
5900 2100
WH 46
WH 65
CONCENTRIC PIPE Ø 80/125
(C13-C33-C43)
Pipes length (m)
Parametres
H536-H613
Parametres
H612
Max heat output (rpm) Min heat output (rpm)
(*) 0 - 4
6000 1850
5 - 10
6500 2100
(*) Default setting parameters