Pentax N-0751M-OD Water Heater User Manual


 
14
Vertical Vent Termination
Firestop
Firestop/
Support
Roof
Flashing
Roof
Jack
Storm
Collar
Rain
Cap
Hanger
Strap
Elbow
Condensation
Drain (Install
According to
Local Codes)
Appliance
Adapter*
* Adapter not required when
using Noritz N-Vent.
**0.3m (1') Min. -
0.9m (3') Max.
** 0.3m (1') minimum recommended,
but not required. Avoid installing
elbow directly on flue.
Terminate at least 1.8m (6') from the combus-
tion air intake of any appliance, and 0.9m (3')
from any other building opening, gas utility
meter, service regulator etc.
Enclose exterior vent systems below the roof
line to limit condensation and protect against
mechanical failure.
When the vent penetrates a floor or ceiling and
is not running in a fire rated shaft, a firestop and
support is required.
Terminate the vent system at least 0.6m (2')
above, but not more than 1.8m (6') above the
roof line, or according to the vent pipe
manufacturer's instructions.
Terminate the vent system at least 0.6m (2')
above any portion of a building located within
3m (10') horizontally.
Provide vertical support every 3.6m (12') or as
required by the vent pipe manufacturer's in-
structions.
Slope the horizontal vent 1/4" for every 300m
(12") towards the drain tee.
Do not vent straight upwards.
Always have a horizontal section of venting.
Install a condensation drain in the horizontal
section of the venting.
Horizontal Vent Termination
Terminate at least 300mm (12") above
grade or above snow line.
Terminate at least 2.1m (7') above a public
walkway, 1.8m (6') from the combustion air
intake of any appliance, and 0.9m (3') from
any other building opening, gas utility meter,
service regulator etc.
Terminate at least 0.9m (3') above any
forced air inlet within 3m (10'), 1.2m (4') be-
low, 1.2m (4') horizontally from or 0.3m (1')
above any door, window, or gravity air inlet
into any building per National Fuel Gas Code
ANSI Z223.1/NFPA 54.
Slope the horizontal vent 1/4" downwards
for every 300m (12").
Use a condensation drain if necessary.
•In the Commonwealth of Massachusetts a
carbon monoxide detector is required for all
side wall horizontally vented gas fuel equip-
ment. Please refer to Technical Bulletin TB
010606 for full installation instructions.
Appliance
Adapter*
Elbow
Hanger
Straps
Wall
Thimble
Ter mination
**0.3m (1') Min. -
0.9m (3') Max.
Slope vent
Downwards
* Adapter not required when
using Noritz N-Vent.
** 0.3m (1') minimum recommended,
but not required. Avoid installing
elbow directly on flue.
07.1.5, 4:34 PMPage 14