Outing function is a function that prevents the room temperature from increasing too much (or
decreasing too much) when no one is in the room.
An air conditioner works automatically if this function is set effective.
3. Outing Function
COOL / DRY
The air conditioner starts operation when the room
temperature increases up to –1°C of the upper
limit.
The air conditioner stops operation when the room
temperature decreases up to –2°C of the upper
limit.
Room temperature
Outing function upper limit
HEAT
The air conditioner starts operation when the room
temperature decreases up to +1°C of the lower
limit.
The air conditioner stops operation when the room
temperature increases up to +2°C of the lower
limit.
Room temperature
Outing function Lower limit
General Performance of the Outing Function
[Precautions]
The outing control only starts/stops the air conditioner. It does not change the operation mode/
 temperature setting.
 Therefore, the operation mode/temperature needs to be set beforehand so that the outing function
 turns on the air conditioner with your desired operation mode/ temperature setting.
If the room temperature rapidly changes, the room temperature may get over the upper or lower limit
 when the outing function is activated.
The outing function is invalid during FAN/AUTO operation mode.
The air conditioner’s stop order (stated in above) is valid only when the outing function is
 operated.
If operated using other remote control units (or a centralized control device such as a system control),
the outing function will not stop air conditioner operation.