12.11 Room Freeze Protection Function (RFP) Operation
When the RFP is selected, the unit will operate the fan at high speed for proper room temperature monitoring.
When the sensor detects that the room temperature has dropped below 46°F / 8°C, the compressor/heat pump
operation begins.
When the room temperature reaches 50°F / 10°C, the unit shuts off, then will repeat continuously if the
temperature drops below 46°F / 8°C again.
<Disclaimer>
This function may not be performed if the unit is not energized, or under a certain condition that unit is unable to
operate such as in protection mode. Please consult with the HVAC installers or professional for details.
The Room Freeze Protection function (RFP) cannot be used unless the unit is energized and set into the RFP
mode.
In the advent of a power failure this mode will not function. During the RFP mode, POWERFUL OPERATION,
QUIET OPERATION and FAN SPEED selection are all disabled. Please consult with your HVAC installer or
professional for more details.
12.12 AUTO COMFORT and ECONAVI Operation
Area of human availability, activity level and absent is judged based on pulses by using 2 infrared sensors. The
internal setting temperature shift, fan speed and horizontal airflow direction are adjusted in order to provide
comfort environment while maintain the energy saving level.
AUTO COMFORT start condition:
o When AUTO COMFORT button is pressed.
AUTO COMFORT stop conditions:
o When AUTO COMFORT button is pressed again.
o When unit is OFF by OFF/ON button.
o When unit is OFF when OFF TIMER activates.
o When unit is OFF by AUTO OFF/ON button at indoor unit.
o When POWERFUL, QUIET operation activates.
ECONAVI start condition:
o When ECONAVI button is pressed.
ECONAVI stop conditions:
o When ECONAVI button is pressed again.
o When unit is OFF by OFF/ON button.
o When unit is OFF when OFF TIMER activates.
o When unit is OFF by AUTO OFF/ON button at indoor unit.
o When POWERFUL, QUIET operation activates.