12.5 Outdoor Fan Speed Control
There is only one speed for outdoor fan motor. (Applicable for CU-C18KK)
There is 2 speeds for outdoor fan motor. Outdoor fan speed can be changed to Hi or Lo according to outdoor
temperature. (Applicable for CU-C24KK).
For Cooling and Soft Dry operation, when outdoor temperature reaches to 31°C (Hi-speed), 29°C (Lo-speed).
(Applicable for CU-C24KK).
When air conditioner is turned on, the compressor and the outdoor fan will operate simultaneously.
Likewise, both compressor and outdoor fan will stop at the same time if the unit is turned off.
12.6 Vertical Airflow Direction Control
12.6.1 Auto Control
When the vertical airflow direction is set to Auto using the remote control, the louver swings up and down as
shown in the diagram.
When stops operation using the remote control, the discharge vent is reset and stops at the closing position.
During Cooling operation or Soft Dry operation, indoor fan motor may stop to rotate at certain periods. At that
condition, the louver will stop swinging.
12.6.2 Manual Control
When the vertical airflow direction is set to Manual using the remote control, the automatic airflow is released and
the airflow direction louver move up and down in the range shown in the diagram.
The louver can be adjusted by pressing the button to the desired louver position.
When stop operation using the remote control, the discharge vent is reset, and stop at the closing position.
Upper limit for cooling mode
and soft dry mode/17°
28°
Closing
position
/ 148°
Swing up and down
Lower limit for cooling mode and
soft dry mode/45°
Horizontal
Upper limit/0°
Closing
position
/ 148°
Lower limit for cooling mode
and soft dry mode
Horizontal
17°
22°
33°
28°
39°
Upper limit for
cooling mode and
soft dry mode
Upper limit / 0°