Nortec Industries None Humidifier User Manual


 
-9-
Set MODBUS
parity *
Change the humidifier controller’s
MODBUS parity.
Range is None, Even, Odd
This setting shall be non-volatile with a
default setting of Even.
40554
The value changes will only take
effect following a hardware reset
of the control board
Reset Run
Hour Counter
Resets the humidifier controller’s run
hour counter to zero hours
40560
255 will start the run hours
counter process.
0 will be accepted to clear the run
hours counter.
Current
damping
Buffers the measured current 40910 From 0 to maximum (depending
on software ability)
Electrode
current
The value of the electrode current in
Amps
30850
Hex value representing the
humidifies current in amps
Resolution: 0.10 amps
Example:
015F (hex) = 35.1 Amps
Steam output The current steam output in Kg/Hr. or
LBS/hr
See UNITS (Modbus 40031)
30860
Hex value representing the
humidifies steam output in kg/hr
Resolution: 0.10 kg or LBS
Example:
013B (hex) = 31.5 kg/hr or
LBS/hr
Run hour
counter
The number of hours the humidifier
has been in operation since the last
time the run hour counter was reset
30414
Hex value representing the
number of humidifier operational
hours since the last reset.
Resolution: 5 minutes
Maximum count: 5460 Hours.
Example:
07D0 = 2000 hours
Firmware
version
The firmware version of the humidifier
controller
30361
PackedBCDversion3.52would
be 0x0352
Humidifier state Describes the current state of the
humidifier and it’s I/O’s
Contactor ON/OFF
Fill Valve ON/OFF
Drain Valve ON/OFF
30800
Bit Allocation
Note More than one bit can be
active at any time.
Contactor on = 1
Fill valve on = 2
Drain valve on = 4