10-30
Page 82
2008-10-01
Unit Model NH 005-020 NH 030 NH 045-100 NH 135-200
Distributor Model
ASD BSD CSD CSD
No. of Cylinders
1 1 1 2
No. of Outlets/Cylinder
1 1 1 2
OD of Cylinder Outlet (NHTC,P,B)
f" f" f" 1¾"
OD of Cylinder Outlet (NHSC/DI)
1¾" 1¾" 1¾" 1¾"
Distributor
Model
Dimensions – in.(mm) Minimum Duct
A
B
L
Length –
in. (mm)
D
ASD 12 2 (51) 1.75 (44) 10 (254) 12 (305)
ASD18 2 (51) 1.75 (44) 16 (406) 18 (457)
ASD 24 2.25 (57) 1.75 (44) 20 (508) 24 (609)
ASD 30 2.25 (57) 1.75 (44) 26 (660) 30 (762)
ASD 36 2.25 (57) 1.75 (44) 32 (813) 36 (914)
ASD 42 2.5 (64) 2 (51) 38 (965) 42 (1066)
ASD 48 2.5 (64) 2 (51) 44 (1118) 48 (1219)
ASD 54 2.5 (64) 2 (51) 50 (1270) 54 (1371)
ASD 60 3 (76) 2.5 (64) 56 (1422) 60 (1524)
ASD 66 3 (76) 2.5 (64) 62 (1575) 66 (1676)
Figure 6. Distributor Dimensions (Sheet 1 of 3)