Nortec NHPC Humidifier User Manual


 
10-10
Page 52
2008-10-01
Table 22. Ceiling and Frontal Clearances for Blower Packs
NH Series Model
Minimum Number Of
Blower Packs
Minimum Ceiling Clearance
in. (cm)
Minimum Front Clearance
in. (cm)
005 1 18 (45) 30 (76)
010 1 18 (45) 30 (76)
020 1 18(45) 36 (91)
030 1 18 (45) 72 (183)
050 1 36 (91) 84 (213)
075 1 42 (106) 144 (366)
100 1 48 (122) 156 (396)
150 2* 42 (106) 144 (396)
200 2* 48 (122) 156 (396)
NOTES: 1. Remote mounted only. Four remote mounted blower packs are recommended on the 200 model.
2. Clearances based on 72°F at 35% RH.