10-10
Page 33
2008-10-01
Table 11. Steam Line Material
Table 12. Recommended Material and Size for Steam Run
Table 13. Recommended Condensate Line at Distributor(s)
Steam Hose Copper Tube Stainless Steel Tube
Short run < 10 feet (3 m) yes yes yes
Long run > 10 feet (3 m) yes yes
NOTE: Steel, Iron and aluminum tubing or pipe must not be used for the steam distribution lines with these humidifiers.
Plastic tubing and pipe also must not be used for steam distribution lines.
Load Steam Run
Steam Line
Material
Steam Line
Description
lb/hr kg/hr ft m
0-30 0-13 0-10 0-3 Copper Tube ¾" MED-L
Tubing
(f" OD)
0-30 0-13 10 + 3 + Copper Tube 1"MED-L Tubing
(1c" OD)
0-30 0-13 0-10 0-3 Stainless Steel
Tube
f" Tube x
0.049" thick.
0-30 0-13 10 + 3 + Stainless Steel
Tube
1c"Tube x
0.049” thick.
30-100 13-45 0-20 0-6 Copper Tube 1½" MED-L
Tubing (1e"
OD)
30-100 13-45 20 + 6 + Copper Tube 2"MED-L Tubing
(2c"OD)
30-100 13-45 0-20 0-6 Stainless Steel
Tube
1¾" Tube x
0.065" thick.
30-100 13-45 20 + 6 + Stainless Steel
Tube
2" Tube x
0.065" thick.
NOTE: Options shown in a bold-italic font require that reducers be used at both ends. These extra large sizes are to
allow for better condensation removal in long steam runs. These sizes do not permit the use of hose couplings
to connect either humidifier or distributors.
NOTE: Insulate all copper or stainless steel steam lines with minimum one inch high temperature insulation.
Dispersion Method Condensate Hose Copper Tube Stainless Steel Tube
1 x Steam Distributor d" NORTEC 1328840 ¼" MED-L Tubing (d"
OD)
d" Tube 0.049" thick.
3 x Steam Distributor* d" NORTEC 1328840 ½" MED-L Tubing
(f
" OD)
e" Tube 0.049" thick
NOTE: When using more than one distributor, the condensate line should be trapped before it is joined together.