Napoleon Fireplaces GDS25P Electric Heater User Manual


 
13
W415-0547 / C / 07.25.06
VERTICAL TERMINATION
Example 3:
V
1
= 5 ft
V
2
= 10 ft
V
T
=
V
1
+
V
2
=
5 + 10 = 15 ft
H
1
= 3 ft
H
2
= 2.5 ft
H
R
= H
1
+ H
2
= 3 + 2.5 = 5.5 ft
H
O
= .03(one 45º elbow + three 90º elbows - 135º)
= .03(45+90+90+90-135)=5.4
H
T
= H
R
+ H
O
= 5.5 + 5.4 = 10.9 ft
H
T
+ V
T
= 10.9 + 15 = 25.9 ft
Formula 1: H
T
< V
T
10.9 < 15
Formula 2: H
T
+ V
T
< 40 feet
25.9 < 40
Since both formulas are met, this vent con guration is
acceptable.
when (H
T
) < (V
T
)
FIGURE 9
REQUIRED VERTICAL RISE
IN FEET (V
T
)
HORIZONTAL VENT RUN
PLUS OFFSETS IN FEET
FIGURE10
For vent con gurations requiring more than one 45º and one
90° elbow , the following formulas apply:
Formula 1: H
T
< V
T
Formula 2: H
T
+ V
T
< 40 feet
See graph to determine the required vertical rise V
T
for the
required horizontal run H
T
.
90°
90°
V
1
H
1
H
2
V
2
45°
45°
90°
20
10
0 5 10 15
90
100
120
110
30
40
50
60
70
80
130
140
150
20
The shaded area within the lines represents acceptable
values for H
T
and V
T
.