Ensure that minimum clearances shown in Figures 4 through 7 are maintained. Left and right clearances are
determined when facing the front of the firebox.
Follow these instructions carefully to ensure safe installation. Failure to follow these requirements may create a
fire hazard.
1. The clearance from the inside of the appliance to any combustible wall should not
be less than 9". SeeFigure4.
2. The ceiling must be at least 42” from the top of the firebox opening. SeeFigure4.
3. The appliance may be placed against a combustible back wall.
Continuedonpage10