Mitsubishi P264 Air Conditioner User Manual


 
[ VIII Test Run Mode ]
- 141 -
HWE09120 GB
(2) Heating operation
Operation
Outdoor unit model
PUHY-P168TSJMU-A
PUHY-P72TJMU-A PUHY-P96TJMU-A
Operating
conditions
Ambient
tempera-
ture
Indoor
DB/WB
21.1°C/ - [70°F/ - ]
Outdoor
8.3°C/6.1°C [47°F/43°F]
Indoor
unit
No. of connected
units
Unit
4
No. of units in opera-
tion 4
Model - 36/36/48/48
Piping
Main pipe
m [ft]
5 [16-3/8 ]
Branch pipe 10 [32-3/4 ]
Total pipe length 45 [147-5/8]
Fan speed - Hi
Amount of refrigerant
kg
[lbs-oz] 17 [37]
Outdoor
unit
Electric current A 40.8
Voltage V 230
Compressor frequency Hz 53 71
LEV open-
ing
Indoor unit
Pulse
332/332/406/406
SC (LEV1) 0
LEV2 2100 2100
Pressure
High pressure (after O/S)/low
pressure (before accumulator)
MPa
[psi] 2.72/0.66 [395/95] 2.72/0.66 [395/95]
Temp. of
each sec-
tion
Outdoor
unit
Discharge (TH4)
°C [°F]
72 [162] 75 [167]
Heat exchanger out-
let (TH3) 0 [32] -2 [28]
Accumulator inlet 0 [32] -2 [28]
Accumulator outlet 0 [32] -2 [28]
Compressor inlet 0 [32] -2 [28]
Compressor shell
bottom 40 [104] 40 [104]
Indoor
unit
LEV inlet 37 [98] 37 [98]
Heat exchanger
inlet 72 [161] 72 [161]