Mitsubishi Electronics PUHY-P72 Air Conditioner User Manual


 
[ VII Control ]
- 94 -
HWE08040 GB
3. Function of the switch <Remote controller>
(1) MA remote controller (PAR-20MAA)
The SW is located at the bottom of the remote controller under the cover. Operate the switches to perform the remote con-
troller main/sub setting or other function settings. Normally, do not change the settings of switches other than the SW1 (main/
sub switching switch). (All the switches are set to "ON" at factory setting.)
The MA remote controller (PAR-21MAA) does not have the switches listed above. Refer to the installation manual for the func-
tion setting.
Remote controllerSwitching switch
1
ON
234
Switch
2
1
Function
Remote controller
main/sub setting
At power on of the
remote controller
Normal
startup
Timer mode
startup
3
Cooling/heating display
set by automatic setting
Displayed Not displayed
4
Suction temperature display
(discharge temperature display)
Displayed Not displayed
Operation by switch settings
Switch setting timing
ON OFF
Main Sub
Before power on
Before power on
Before power on
Before power on
When two remote controllers are connected
to one group, set either of the remote
controllers to "Sub".
When the program timer (only few stock
products are available) is connected, set to
"Timer mode startup" to resume the operation
with timer mode after power is restored.
When the automatic mode is set and the
"Cooling"/"Heating" display is not necessary,
set to "Not displayed".
When the suction temperature (discharge
temperature) display is not necessary,
set to "Not displayed".