Mitsubishi Electronics PUHY-P360Y(T)SHMU-A Air Conditioner User Manual


 
[ VII Control ]
- 89 -
HWE08040 GB
VII Control
[1] Functions and Factory Settings of the Dipswitches
1. Outdoor unit
(1) Control board
1) Unless otherwise specified, leave the switch to OFF where indicated by "-," which may be set to OFF for a reason.
2) A: Only the switch on either the OC or OS needs to be set for the setting to be effective on both units.
B: The switches on both the OC and OS need to be set to the same setting for the setting to be effective.
C: The setting is effective for the unit on which the setting is made.
3) Refer to "VII [2] Controlling the Outdoor Unit" for details.(page 96)
4) The table below shows the combination of SW2-9 and SW3-5 settings and the target evaporation temperature setting that
corresponds to each combination.
Switch Function
Function according to switch setting Switch setting timing
Units that re-
quire switch
setting
Note.2
OFF ON OFF ON OC OS
SWU 1-2 Unit address setting Set to 00 or 51-100 with the dial switch Before power on C C
SW1 1-10
For self-diagnosis/
operation monitoring
Refer to the LED monitor display on the
outdoor unit board.
Anytime after power on
CC
SW2
1
Centralized control
switch
Without connection
to the centralized
controller
With connection to
the centralized con-
troller
Before power on
BB
2
Deletion of connec-
tion information
Normal control Deletion Before power on
A-
3
Deletion of error his-
tory SW
(OC) Storage of IC/
OC error history
(OC) Deletion of IC/
OC error history
Anytime after power on
(When switched from OFF
to ON)
CC
(OS) Storage of OS
error history
(OS) Deletion of
OS error history
4 Pump down mode Normal control Pump down mode
After being energized and
while the compressor is
stopped
A-
5- - - - --
6- - - - --
7
Forced defrost
Note 3
Normal control
Forced defrost
starts
10 minutes
after com-
pressor
startup
Anytime af-
ter power
on (When
switched
from OFF to
ON)
AA
8
Defrost timer setting
Note 3
50 minutes 90 minutes
Anytime after power on
(When switched from OFF
to ON)
BB
9
Target evaporation
temperature setting
Depends on the setting combination with
the SW3-5 setting (Note 4)
Anytime after power on
A-
10
Enable/disable re-
frigerant noise sup-
pression function
during defrosting
(Fan operation
against leaky indoor
unit LEV)
Normal control
Refrigerant noise
suppression
Befo
re powe
r on
A-
Switch
SW2-9
OFF ON
SW3-5 OFF 0°C [32°F] -4°C [25°F]
ON -2°C [28°F] -6°C [21°F]