Mitsubishi Electronics PUHY-P360Y(T)SHMU-A Air Conditioner User Manual


 
[ VIII Test Run Mode ]
- 141 -
HWE08040 GB
Operation
Outdoor unit model
PUHY-P360TSHMU-A
PUHY-
P120THMU-A
PUHY-
P120THMU-A
PUHY-
P120THMU-A
Operating
conditions
Ambient
tempera-
ture
Indoor
DB/WB
26.7°C/19.4°C [80°F/67°F]
Outdoor
35°C/ - [95°F/ - ]
Indoor
unit
No. of connected
units
Unit
7
No. of units in opera-
tion 7
Model - 48/48/48/54/54/54/54
Piping
Main pipe
m [ft]
5 [16-3/8 ]
Branch pipe 10 [32-3/4 ]
Total pipe length 75 [246-1/16]
Fan speed - Hi
Amount of refrigerant
kg
[lbs-oz] 39 [86]
Outdoor
unit
Electric current A 87.1
Voltage V 230
Compressor frequency Hz 74 74 74
LEV open-
ing
Indoor unit
Pulse
325/325/325/387/387/387/387
SC (LEV1) 171 171 171
LEV2 1400 1400 1400
Pressure
High pressure (after O/S)/low
pressure (before accumulator)
MPa
[psi]
2.92/0.90 2.92/0.90 2.92/0.90
[424/131] [424/131] [424/131]
Temp. of
each sec-
tion
Outdoor
unit
Discharge (TH4)
°C [°F]
73 [163] 73 [163] 73 [163]
Heat exchanger out-
let (TH3) 40 [104] 40 [104] 40 [104]
Accumulator inlet 10 [50] 10 [50] 10 [50]
Accumulator outlet 10 [50] 10 [50] 10 [50]
SCC outlet (TH6) 20 [68] 20 [68] 20 [68]
Compressor inlet 15 [59] 15 [59] 15 [59]
Compressor shell
bottom 42 [108] 42 [108] 42 [108]
Indoor
unit
LEV inlet 19 [66] 19 [66] 19 [66]
Heat exchanger