Mitsubishi Electronics PUHY-P288 Air Conditioner User Manual


 
- 30 -
[ II Restrictions ]
GBHWE08040
(4) Wiring method
1) Indoor/outdoor transmission line
Same as [5] 1.
Shielded cable connection
Same as [5] 1.
2) Transmission line for centralized control
No connection is required.
3) MA remote controller wiring
Same as [5] 1.
When 2 remote controllers are connected to the sys-
tem
Same as [5] 1.
Group operation of indoor units
Same as [5] 1.
4) LOSSNAY connection
Connect terminals M1 and M2 on the terminal block
(TB5) on the indoor unit (IC) to the appropriate terminals
on the terminal block (TB5) on LOSSNAY (LC). (Non-po-
larized two-wire)
Interlock setting between the indoor units and LOSS-
NAY units must be entered on the remote controller. (Re-
fer to "IV [3] Interlock Settings via the MA Remote
Controller" or the installation manual for the MA remote
controller for the setting method.)
5) Switch setting
Address setting is required as follows.
(5) Address setting method
The outdoor units in the same refrigerant circuit are automatically designated as OC, OS1, and OS2.
Proce-
dures
Unit or controller
Address
setting
range
Setting method Notes
Factory
setting
1 Indoor unit Main
unit
IC 01 to 50 Assign the smallest ad-
dress to the main unit in the
group.
To perform a group opera-
tion of indoor units that
have different functions,
designate the indoor unit
in the group with the great-
est number of functions as
the main unit.
00
Sub unit Assign sequential numbers
starting with the address of
the main unit in the same
group +1. (Main unit ad-
dress +1, main unit ad-
dress +2, main unit
address +3, etc.)
2 LOSSNAY LC 01 to 50 Assign an arbitrary but
unique address to each of
these units after assigning
an address to all indoor
units.
None of these addresses
may overlap any of the in-
door unit addresses.
00
3MA
remote con-
troller
Main
remote
control-
ler
MA No
settings re-
quired.
-Main
Sub
remote
control-
ler
MA Sub
remote
controller
Settings to be made ac-
cording to the remote con-
troller function selection
4 Outdoor unit OC
OS1
OS2
51 to 100 Assign sequential address
to the outdoor units in the
same refrigerant circuit.
The outdoor units are auto-
matically designated as
OC, OS1, and OS2.(Note)
To set the address to 100,
set the rotary switches to
50.
00