[ VIII Test Run Mode ]
- 132 -
HWE08040 GB
(2) Heating operation
Operation
Outdoor unit model
PUHY-P144TSHMU-A
PUHY-P72THMU-A PUHY-P72THMU-A
Operating
conditions
Ambient
tempera-
ture
Indoor
DB/WB
21.1°C/ - [70°F/ - ]
Outdoor
8.3°C/6.1°C [47°F/43°F]
Indoor
unit
No. of connected
units
Unit
4
No. of units in opera-
tion 4
Model - 36/36/36/36
Piping
Main pipe
m [ft]
5 [16-3/8 ]
Branch pipe 10 [32-3/4 ]
Total pipe length 45 [147-5/8]
Fan speed - Hi
Amount of refrigerant
kg
[lbs-oz] 19 [42]
Outdoor
unit
Electric current A 32.6
Voltage V 230
Compressor frequency Hz 51 51
LEV open-
ing
Indoor unit
Pulse
332/332/332/332
SC (LEV1) 0
LEV2 1400 1400
Pressure
High pressure (after O/S)/low
pressure (before accumulator)
MPa
[psi] 2.59/0.67 [376/97] 2.59/0.67 [376/97]
Temp. of
each sec-
tion
Outdoor
unit
Discharge (TH4)
°C [°F]
72 [162] 72 [162]
Heat exchanger out-
let (TH3) 0 [32] 0 [32]
Accumulator inlet 0 [32] 0 [32]
Accumulator outlet 0 [32] 0 [32]
Compressor inlet 0 [32] 0 [32]
Compressor shell
bottom 40 [104] 40 [104]
Indoor
unit
LEV inlet 36 [97] 36 [97]
Heat exchanger
inlet 70 [158] 70 [158]