Mitsubishi Electronics PUHY-P288 Air Conditioner User Manual


 
[ II Restrictions ]
- 20 -
HWE08040 GB
2. M-NET Address settings
(1) Address settings table
The need for address settings and the range of address setting depend on the configuration of the system.
*1. Address setting is not required for a City Multi system that consists of a single refrigerant circuit (with some exceptions).
*2. To set the M-NET remote controller address to "200", set the rotary switches to "00".
*3. To set the outdoor unit address to "100," set the rotary switches to "50."
*4. Some indoor units have 2 or 3 controller boards that require address settings.
No. 2 controller board address must be equal to the sum of the No. 1 controller board address and 1, and the No.3
controller board address must equal to the No. 1 controller address and 2.
*5. The outdoor units in the same refrigerant circuit are automatically designated as OC, OS1, and OS2 in the order of
capacity from large to small (if two or more units have the same capacity, in the order of address from small to large).
Unit or controller Address setting
range
Setting method Facto-
ry set-
ting
CITY MULTI in-
door unit
Main/sub unit 00,
01 to 50
*1
Assign the smallest address to the main indoor unit in the
group, and assign sequential address numbers to the rest
of the indoor units in the same group.
*4
00
M-NET adapter
M-NET control in-
terface
Free Plan adapt-
er
LOSSNAY, OA processing unit
Air handling kit
00,
01 to 50
*1
Assign an arbitrary but unique address to each of
these units after assigning an address to all indoor
units.
00
M-NET remote
controller
Main remote
controller
101 to 150 Add 100 to the smallest address of all the indoor units
in the same group.
101
Sub remote
controller
151 to 200
*2
Add 150 to the smallest address of all the indoor units
in the same group.
MA remote controller No address settings required. (The main/sub setting must be made if 2
remote controllers are connected to the system.)
Main
CITY MULTI outdoor unit 00,
51 to 100
*1,*3
Assign sequential addresses to the outdoor units in the
same refrigerant circuit. The outdoor units in the same
refrigerant circuit are automatically designated as OC
and OS.
*5
00
System controller Group remote
controller
201 to 250 Assign an address that equals the sum of the smallest
group number of the group to be controlled and 200.
201
System remote
controller
Assign an arbitrary but unique address within the
range listed on the left to each unit.
ON/OFF re-
mote controller
Assign an address that equals the sum of the smallest
group number of the group to be controlled and 200.
Schedule timer
(compatible
with M-NET)
Assign an arbitrary but unique address within the
range listed on the left to each unit.
202
Central con-
troller
G(B)-50A
000,
201 to 250
Assign an arbitrary but unique address within the
range listed on the left to each unit. The address must
be set to "000" to control the K-control unit.
000
LM adapter 201 to 250 Assign an arbitrary but unique address within the
range listed on the left to each unit.
247