Mitsubishi Electronics PEFY-AF1200CFM Air Conditioner User Manual


 
4
[Fig. 7.3.1]
A
B
F
C
D
E
A Insert pump's end 2 to 4 cm [13/16 to 1-19/32 in.].
B Remove the water supply port.
C About 2 L
D Water
E Filling port
F Screw
[Fig. 7.3.2]
<Indoor controller board>
7.2
7.3
B
J
O
N
F
Max. 300 mm [11-13/16 in.]
[Fig. 7.2.1]
[Fig. 7.2.2]
Max. 20m [65 ft]
1.5-2 m [5 to 7 ft]
C
B
A
L
D
D
D
E
K
M
B
H
I
G
F
FF
B
C
DE E
H
G
K
J
F
I
A
25 [1] 25 [1]
35
[1-13/32]
A Indoor unit
B Insulation (long) (accessory)
C Tie (long) (accessory)
D Visible part
E Insertion margin
F Drain hose (accessory)
G Drain pipe (O.D. ø32 mm [1-1/4 in.] PVC, field supplied)
H Insulation (field supplied)
I Tie (short) (accessory)
J Max.180 ± 5 mm [7-3/32 ± 7/32 in.]
K The joint of the insulation must be positioned up.
[Fig. 7.2.3]
A Indoor unit
B Insulation (short) (accessory)
C Tie (short) (accessory)
D Attaching the band
E Insertion margin
F Drain hose (accessory)
G Drain pipe (O.D. ø32 mm [1-1/4 in.] PVC, field supplied)
H Insulation (field supplied)
I Max.145 ± 5 mm [5-23/32 ± 7/32 in.]
D
E
H
G
I
F
B
C
5
[7/32]
A
25 [1]
(Unit: mm [in.])
(Unit: mm [in.])
SWE
Correct piping
Wrong piping
A Insulation (9 mm [3/8 in.] or more)
B Decline (1/100 or more)
C Support metal
K Air release tube
L Tr ap
M Odor trap
Drain pipe system
D O. D. ø32 mm [1-1/4 in.] PVC TUBE
E Make it as large as possible. About 10 cm [3-15/16 in.].
F Indoor unit
G Make the piping size large for drain pipe system.
H Decline (1/100 or more)
I O. D. ø38 mm [1-1/2 in.] PVC TUBE for drain pipe system.
(9 mm [3/8 in.] or more insulation)
J Up to 550 mm [21-21/32 in.]
N Drain hose (accessory)
O Horizontal or slightly upgradient