OC277-25
w8 ~ 9 Refer to page OC277-24.
w12 When room temperature is 64°F or below, the compressor cannot operate.
When room temperature rises over 64°F, the compressor starts after a 3-minute time delay.
w13 Compressor ON time is decided by room temperature. Refer to page OC277-33.
w14 In dry operation, compressor ON makes the fan speed LOW and compressor OFF stops the fan.
It is not possible to set the fan speed with the remote controller
DRY OPERATION
DRY
operation
Four-way valve / OFF
Initial dry
operation
Room temperature is
64°F or lower
During
compressor ON
Compressor &
thermostat ON
Vane initial setting
Vane
setting notch
10-minute compressor
OFF timer start
Compressor OFF
Fan STOP
3-minute
time delay
10-minute
compressor
OFF
Compressor ON
time set
Compressor ON
Fan speed LOW
1
Compressor &
thermostat
ON
3-minute
compressor
operation
Compressor ON
time completes
NO
YES
NO
NO
YES
w 14
w 14
w 13
YES
YES
NO
YES
NO
NO
w 9
YES
YES
w 9
NO
NO
w 12
YES
NO
YES
w 8