*1 The power consumption coefticient of the Smart ME Controller is “0.5” and that of a ME Remote Controller
(PAR-F27MEA) is “0.25”.
If the number of Smart ME Controllers is high and the total power supply they require exceeds the outdoor unit's
ability to supply power, a Transmission booster (PAC-SF46EPA) will be required.
*1: "7" for the P200 and P250 models
(1) Wiring from the remote controller
Connect to TB5 (terminal block for indoor-outdoor transmission cable) on any indoor unit in same
M-NET system.
The terminal block has no polarity. Connect to the terminals M1 and M2.
(2) Operating in a group (Groups 01, 02, 03, and 04)
Assign the lowest address to the main indoor unit in the group.
The remote controller address should be set to a number that equals the main indoor unit address
plus 100.
(3) Up to two remote controllers (main and sub) can be connected to an indoor unit or a group of
indoor units.
Connect the main and sub remote controllers in the same way as described in (1) above.
Be sure to set the main and sub remote controller addresses.
The sub remote controller address should be set to a number that equals the main indoor unit
address plus 150.
4 System diagram
Outdoor unit Transmission booster Indoor unit Smart ME Controller
32 25 1
(*1)
0.5
CAUTION
- Remote controllers cannot be wired together. Only one
cable can be connected to the remote controller terminal
block.
- The ME remote controller and MA remote controller
cannot be connected in the same group.
051
TB7 TB3 TB5
001
TB5
002
TB5
003
TB5
004
101 102 104
056
TB7 TB3 TB5
009
TB5
008
TB5
007
TB5
006
107
157
CENTRALIZED CONTROLLER AG-150A
201
000
Outdoor unit
Smart ME
Controller *1
Indoor unit
Indoor unit
Smart ME
Controller
Indoor unit
Indoor unit
Smart ME
Controller
Indoor unit
Smart ME
Controller
Smart ME
Controller
Indoor unit
Indoor unit
Indoor unit
Outdoor unit
Centralized
controller
Power supply
unit
LOSSNAY unit
005
Advanced HVAC
CONTROLLER (AHC)
Group 01
Group 02
Group 03
Group 04
Main
remote
controller
Sub
remote
controller
WT06829X02.book Page 5 Wednesday, June 26, 2013 4:03 PM