1-3. AUTO VANE OPERATION
1. Horizontal vane
<SWING operation>
In swing operation of ECONO COOL operation mode, the initial air flow direction is adjusted to “Horizontal”.
According to the temperature of indoor coil thermistor RT12 at starting of this operation, next downward blow time is
decided. Then when the downward blow has been finished, next horizontal blow time is decided.
For initial 10 minutes the swing operation is performed in table G~H for quick cooling.
Also, after 10 minutes when the difference of set temperature and room temperature is more than 3.6 degrees, the
swing operation is performed in table D~H for more cooling.
The air conditioner repeats the swing operation in various cycle as follows.
ECONO COOL ( ) operation (ECONOmical operation)
When ECONO COOL button is pressed in COOL mode, set temperature is automatically set 3.6 degrees higher than
that in COOL mode.
Also the horizontal vane swings in various cycle according to the temperature of indoor heat exchanger (RT12).
SWING operation makes you feel cooler than set temperature. So, even though the set temperature is higher than that
in COOL mode, the air conditioner can keep comfort. As a result, energy can be saved.
ECONO COOL operation is cancelled when ECONO COOL button is pressed once again or VANE CONTROL
button is pressed or change to other operation mode.
Temperature of indoor
coil thermistor RT12
more than 75°F
5
2
Downward blow time
(second)
72°F to 75°F
70°F to 72°F
68°F to 70°F
64°F to 68°F
63°F to 64°F
59°F to 63°F
59°F or less
5
8
11
14
17
20
23
Horizontal blow time
(second)
20
17
14
11
8
2
23
A
H
G
F
E
D
C
B