Fan speed is switched according to the number of operating indoor unit and the compressor frequency.
Note
•When the indoor coil thermistor is 134.6˚F or more on HEAT operation, fan speed is fixed to Low speed.
Or, the indoor coil thermistor is 113˚F or less on HEAT operation, fan speed is back to normal.
3-4. HEAT DEFROSTING CONTROL
(1) Conditions to enter defrosting mode
1. When temperature of defrosting thermistor is 26.6˚F or less.
2. When specified non-defrosting time, is counted in the control p.c. board is satisfied.
(Total time of compressor operating)
Going to defrosting mode at both condition of 1 and 2.
(2) Defrosting operation
1. Compressor stops for 50 seconds, Indoor fan is off, Defrosting lamp lights.
2. 4-way valve reverses flow, Compressor operates by the frequency in heat defrosting control.
3. After compressor stops for 35 seconds, 4-way valve reverses flow, then defrosting finishes.
(3) Conditions to finish defrosting mode
1. When the defrosting thermistor temperature is 55.76˚F or more.
2. When it has spent 10 minutes for defrosting.
Defrosting finishes at condition of 1 or 2.
This protection controls the compressor ON/OFF and operation frequency according to temperature of the discharge
temperature thermistor.
(1) Compressor ON/OFF
When temperature of the discharge temperature thermistor exceeds 240.8˚F, the control stops the compressor.
When temperature of the discharge temperature thermistor is 176˚F or less, the controls starts the compressor.
(2) Compressor operation frequency
When temperature of the discharge temperature thermistor is expected to be higher than 240.8˚F, the control decreases 12Hz
from the current frequency.
When temperature of the discharge temperature thermistor is expected to be higher than 231.8˚F and less than 240.8˚F, the
control decreases 6Hz from the current frequency.
When temperature of the discharge temperature thermistor is expected to be higher than 219.2˚F and less than 231.8˚F, the
control is set at the current frequency.
3-5. DISCHARGE TEMPERATURE PROTECTION CONTROL
3-6. OUTDOOR FAN CONTROL
COOL
Fan speed
Up
Down
Up
Down
Mode
HEAT
Compressor frequency
<Relation between compressor frequency and fan speed.>
40Hz
30Hz
40Hz
30Hz
Up
Down
Fan speed
High
Low
Compressor frequencyMin. Max.