Mitsubishi Electronics MSY-GE15NA Air Conditioner User Manual


 
4
3-2. OUTLET AIR SPEED AND COVERAGE
The air coverage is the figure up to the
position where the air speed is 1 ft./s.,
when air is blown out horizontally from
the unit properly at the High speed posi-
tion.
The coverage should be used only as a
general guideline since it varies accord-
ing to the size of the room and furniture
arranged inside the room.
(2) OPERATION
Mode Condition
Intake air temperature (°F)
Indoor Outdoor
DB WB DB WB
Cooling
Standard temperature 80 67 95
Maximum temperature 90 73 115
Minimum temperature 67 57 14
Maximum humidity 78%
Heating
Standard temperature 70 60 47 43
Maximum temperature 80 67 75 65
Minimum temperature 70 60 -4 -5
3-1. OPERATING RANGE
(1) POWER SUPPLY
Rated voltage Guaranteed voltage (V)
Indoor unit
208/230 V
1 phase
60 Hz
Min. 187
208 230
Max. 253
Model Mode Function
Air ow
(CFM)
Air speed
(ft./s.)
Coverage
(ft.)
MSZ-GE06NA
HEAT Dry 406 20.6 29.5
COOL
Dry 321 16.3 23.5
Wet 286 14.5 21.0
MSZ-GE09NA
MSY-GE09NA
HEAT Dry 406 20.6 29.5
COOL
Dry 321 16.3 23.5
Wet 286 14.5 21.0
MSZ-GE12NA
MSY-GE12NA
HEAT Dry 406 20.6 29.5
COOL
Dry 321 16.3 23.5
Wet 286 14.5 21.0
MSZ-GE15NA
MSY-GE15NA
HEAT Dry 463 23.4 33.5
COOL
Dry 420 21.3 30.5
Wet 385 19.5 28.0
MSZ-GE18NA
MSY-GE18NA
HEAT Dry 512 25.9 36.9
COOL
Dry 420 21.3 30.5
Wet 385 19.5 28.0