Mitsubishi Electronics MS-GD08ND-ci Air Conditioner User Manual


 
8
Table 1
How to set the remote controller exclusively for particular indoor unit
After you turn the breaker ON, the first remote controller that sends the signal to the indoor unit will be regarded as the
remote controller for the indoor unit.
The indoor unit will only accepts the signal from the remote controller that has been assigned to the indoor unit once they
are set.
The setting will be cancelled if the breaker has turned off, or the power supply has shut down.
Please conduct the above setting once again after the power has restored.
7-2. P.C. BOARD MODIFICATION FOR INDIVIDUAL OPERATION
A maximum of 4 indoor units with wireless remote controllers can be used in a room.
In this case, to operate each indoor unit individually by each remote controller, P.C. boards of remote controller must be
modified according to the number of the indoor unit.
7-1. TIMER SHORT MODE
For service, set time can be shortened by short circuit of JPG and JPS the electronic control P.C. board.
The time will be shortened as follows. (Refer to 8-6.)
Set time : 1-minute
1-second
Set time : 3-minute 3-second
It takes 3 minutes for the compressor to start operation. However, the starting time is shortened by short
circuit of JPG and JPS.
How to modify the remote controller P.C. board
Remove batteries before modification.
The board has a print as shown below :
NOTE : For remodelling, take out the bat-
teries
and push the OPERATE/
STOP(ON/OFF)button twice or 3
times at first.
After finish remodelling, put back
the batteries then press the
RESET button.
Remote controller model : MP2B
The P.C. board has the print “J1” and “J2”. Solder “J1” and “J2” according to the number of indoor unit as shown in Table 1.
After modification, press the RESET button.
J2
J1
SERVICE FUNCTIONS
7
MS-GD08ND-
C1
MS-GD10ND-
C1
MS-GD12ND-
C1
1 unit operation 2 units operation 3 units operation 4 units operation
No. 1 unit No modification Same as at left Same as at left Same as at left
No. 2 unit Solder
J1 Same as at left Same as at left
No. 3 unit Solder
J2 Same as at left
No. 4 unit Solder
both J1 and J2