Lochinvar 51 Boiler User Manual


 
8 Field wiring
ELECTRICAL SHOCK HAZARD – For
your safety, turn off electrical power
supply before making any electrical
connections to avoid possible electric
shock hazard. Failure to do so can cause
severe personal injury or death.
Wiring must be N.E.C. Class 1.
If original wiring as supplied with boiler
must be replaced, use only type 105°C
wire or equivalent.
Boiler must be electrically grounded as
required by National Electrical Code
ANSI/NFPA 70 – latest edition.
Installation must comply with:
1. National Electrical Code and any other national, state,
provincial, or local codes, or regulations.
2. In Canada, CSA C22.1 Canadian Electrical Code Part 1,
and any local codes.
3. Wire the boiler pump as shown in FIG. 8-2.
4. When connecting a domestic hot water (DHW) pump,
connect the wiring to the line voltage terminal strip as
shown in FIG. 8-2.
5. To activate a system pump, wire as shown in FIG. 8-2. If the
motor is larger than 1/8 hp or 1.8 amps, you must isolate
with a relay.
Figure 8-2 Line Voltage Field Wiring Connections
Label all wires prior to disconnection
when servicing controls. Wiring errors
can cause improper and dangerous
operation.
ƽ WARNING
NOTICE
ƽ CAUTION
REMOVE BEZE
L
Figure 8-1 Remove Bezel
Low voltage connections
1. Route all low voltage wires through the knockouts in the
bottom front right side, just under the control panel, as
shown in FIG. 8-3.
2. Connect low voltage wiring to low voltage connection board
as shown in FIG. 8-4 on page 53 of this manual and the
boiler wiring diagram.
LOW VOLTAGE
WIRING KNOCKOUTS
LOW VOLTAGE
CONNECTION BOARD
LINE VOLTAGE
WIRING KNOCKOUTS
LINE VOLTAGE
JUNCTION BOX
Figure 8-3 Routing Field Wiring
Line voltage connections
1. Remove bezel as shown in FIG. 8-1.
2. Connect 120 vac power wiring to the line voltage terminal
strip in the junction box, as shown in FIG. 8-2.
2. Provide and install a fused disconnect or service switch
(15 amp recommended) as required by the code (see
FIG. 8-2).
50
Installation & Operation Manual