2 Maintenance schedule
5
ƽ WARNING
Follow the maintenance procedures given throughout this manual. Failure to perform the service and
maintenance or follow the directions in this manual could result in damage to the boiler or system,
resulting in severe personal injury, death, or substantial property damage.
User’s Information Manual
Service technician
(see the Knight XL Service Manual)
General:
Address reported problems
Inspect interior; clean and vacuum
if necessary
Clean condensate trap and ll with
fresh water
Check for leaks (water, gas, ue,
condensate)
• Verify ue and air lines in good
condition and sealed tight
Check system water pressure/
system piping/expansion tank
Check control settings
Check ignition and ame sense
electrodes (sand off any deposits;
clean and reposition)
Check wiring and connections
Perform start-up, checkout and
performance veri cation per Sec-
tion 10 in the Knight XL Installation
and
Operation manual
Flame inspection (stable, uniform)
Flame signal (at least 10
microamps at high re)
Clean the heat exchanger if ue
temperature is more than 54°F
(30°C) above return water
temperature
If combustion or performance
indicate need:
Clean heat exchanger
Remove and clean burner using
compressed air only
Clean the blower wheel
Owner maintenance
(see pages 6 - 8 for detailed instructions)
Daily
Check boiler area
• Check pressure/
temperature gauge
Monthly
Check vent pipng
Check air piping
Check air and vent a
• termination screens
Check relief valve
Check condensate drain
system
Check air vents
Periodically
Test low water cutoff
(if used)
Reset button (LWCO)
Every
6 months
Check boiler piping
(gas and water) for leaks
Operate relief valve
End
of season
months
Shut boiler down
(unless boiler is used for
domestic hot water)
ANNUAL START-UP