Lochinvar 399 Boiler User Manual


 
Installation & Operation Manual
37
6 Hydronic piping (continued)
Figure 6-5 Pressure Drop vs. Flow - Models 399 and 500
Table 6B Sizing Information for Temperature Rise Applications_20°F, 25°F, 30°F and 35°F
Figure 6-6 Pressure Drop vs. Flow - Models 600 thru 800
0
2
4
6
8
10
12
14
16
18
20
0 5 10 15 20 25 30 35 40 45
KBN500
KBN399
Pressure Drop vs Flow
(Includes Boiler Secondary Piping)
Flow Rate (GPM)
Pressure Drop (Feet of Head)
0
10
20
30
40
50
60
0 102030405060708090
KBN800
KBN700
KBN600
Pressure Drop vs Flow
(Includes Boiler Secondary Piping)
Flow Rate (GPM)
Pressure Drop (Feet of Head)
TEMPERATURE RISE APPLICATIONS
Model
MINIMUM
PIPE
SIZE
20°F 25°F 30°F 35°F
GPM FT/HD GPM FT/HD GPM FT/HD GPM FT/HD
399 1 1/2" 37 21 30 14 26 11 21 8
500 1 1/2" 46 23 37 16 32 13 26 10
600 2" 55 31 44 22 38 18 32 13
700 2" 65 30 52 20 45 16 37 11
800 2" 74 33 60 23 51 18 42 12