Lochinvar 210 Boiler User Manual


 
User’s Information Manual
2 Maintenance schedule
5
Service technician
(see the Knight Wall Mount Service Manual)
General:
• Reported problems
• Inspect interior; clean and vacuum if
necessary
• Clean condensate trap and fill with fresh
water
•Check for leaks (water, gas, flue,
condensate)
• Verify flue and air lines in good condition
and sealed tight
•Check system water pressure/system
piping/expansion tank
• Check control settings
Ignition and flame sense electrodes
(sand off any deposits; clean and
reposition)
• Wiring and connections
Perform start-up checkout and
performance verification per Section 10
in the Knight Wall Mount Installation and
Operation Manual.
• Flame inspection (stable, uniform)
• Flame signal (at least 4 mA)
•Clean the heat exchanger if flue
temperature is more than 54°F above
return water temperature.
If combustion or performance
indicate need:
• Clean heat exchanger
Remove and clean burner using
compressed air only
• Clean the blower wheel
Owner maintenance
(see pages 6 - 8 for detailed instructions)
Daily
• Check boiler area
Check pressure/temperature
gauge
Monthly
• Check vent piping
• Check air piping
Check air and vent termination
screens
• Check relief valve
• Check condensate drain system
• Check air vents
Periodically
• Test low water cutoff (if used)
• Reset button (low water cutoff)
Every
6 months
• Check boiler piping (gas and
water) for leaks
• Operate relief valve
End
of season
months
•Shut boiler down (unless boiler
used for domestic hot water)
ƽ WARNING
Follow the maintenance procedures given throughout this manual. Failure to perform the service and
maintenance or follow the directions in this manual could result in damage to the boiler or system,
resulting in severe personal injury, death, or substantial property damage.
ANNUAL START-UP