Lochinvar 2072 Water Heater User Manual


 
3 Troubleshooting
34
FAULT CAUSE CORRECTIVE ACTION
No Display
- No 120 VAC supplied to unit.
• Check external line switch, fuse, or breaker.
• Check position of ON/OFF switch. Turn switch to the
ON position.
• Check 120 VAC through the ON/OFF switch. No
voltage through switch, replace switch.
- Bad wiring connection.
• Check wiring harness connection between the display
board and the main control board. Connect the harness
at both points.
- Blown fuse.
• Replace fuse F6 on the main control board, see
FIG. 3-1 on page 33 of this manual.
- Bad display board. • Replace board.
- Bad main control board. • Replace main control board.
No Burner
Operation
- Main control board temperature setpoint
satisfied.
• Review temperature setting.
- Remote thermostat satisfied.
• Review remote thermostat setting.
- Outside air temperature above Warm
Weather Shutdown (WWSD) setpoint for
main control board.
Check location of outside air sensor. Check
resistance of outdoor air sensor and compare to Table
3C on page 35 of this manual.
- Unit locked out on fault.
• Consult display for specific fault. Refer to fault
descriptions on pages 37 - 43 of this manual for
corrective actions.
Unit Does
Not Stage to
100%
- Boiler controlled by BMS.
Check BMS parameter settings. Optional PC
software required.
- Outlet temperature too high.
- Delta T too high.
Table 3A Troubleshooting Chart - No Display
Copper-fin II/IIE Boiler and Water Heater Service Manual