2. Product does not operate at all.
(* Refer to Electronic Control Device drawing and Schematic diagram.)
Turn off Main Power
Turn on Main Power
Does "beeping" sound is made from the Indoor Unit?
Primarily, the operating condition of Micom is OK.
Check the voltage of power(About AC 208V/AC230V, 60Hz)
Main power's voltage
Voltage applied to the unit
Connecting method of Indoor/Outdoor connecting
cable
Check PWB Ass'y(Outdoor unit)
- Fuse
- Pattern damage
- Varistor(ZNRI)
Check the connection housing for contacting
Connector related to CN-POWER
Connector related to CN-FAN
Connector contacting of Outdoor Fan/Compressor
Display PWB Ass'y Check
Connector related to CN-DC/DC
Check each load(Indoor/Outdoor Fan Motor,
Compressor, Stepping Motor) and contacting
condition of related connector(including connecting
cable of Indoor/Outdoor Unit)
PCB Board Operation Check
Items
Power Transformer
(Outdoor unit)
- Input Voltage
- Output Voltage
IC2(7812) Output
(Indoor/Outdoor unit)
IC3(7805) Output
(Indoor/Outdoor unit)
IC4(KIA7036, Reset IC)
OSC01B(4MHz)
(Indoor/Outdoor unit)
Replace Trans
Replace IC2
Replace IC3
Replace faulty parts
- About AC208V/230V
±
10% - Check the power voltage
- About AC17
±
3V
DC
+
12V
DC
+
5V
Voltage of Outdoor unit Micom No. 8,
Voltage of Indoor unit Micom No. 43 and soldering
condition
Content Remedy
NO
YES
(After 10 seconds)