78 Room Air Conditioner
When compressor does not oprate normally.
■ CT Error (Error Code ➆)
Trouble 8-3
Does the operating LED in Display PCB
Ass'y blink 7 times?
• Check the state of connecting cable
(3 line) bewteen Indoor and Outdoor Unit .
• Check fuse, Noise Filter, PTC, etc.
NO
YES
Is the courrent transformer(CT) in Main
PCB Ass'y right?
Check the PCB pattern(resoldering)
NO
YES
Is the indoor/outdoor fan locked?
Check the indoor/outdoor fan motor.
NO
YES
Is the discharge temperature of Indoor unit
right(11°C~17°C) in the cooling mode?
Check the compressor.
NO
YES
Is the refrigerant pressure right?
Supply the refrigerant or Discharge the
refrigerant.
NO
YES
Replace the PCB Ass'y.
• Main PCB Ass'y(Outdoor)
• Control Box Ass'y(Outdoor)
Troubleshooting Guide