Lennox International Inc. G50UH-48B-090 Furnace User Manual


 
Removingthe Bottom Panel
Remove the two screws that secure the bottom cap to the
furnace. Pivot the bottom cap down to release the bottom
panel. Once the bottom panel has been removed, reinstall
the bottom cap, See figure 9.
Removing the Bottom Panel
Screw
\/
Bottom Cap
Bottom
FIGURE 9
Leveling an Upflow Unit
When the side return air inlets are used in an upflow ap-
plication, it may be necessary to install leveling bolts on the
bottom of the furnace. Use field-supplied corrosion-resist-
ant 5/16 inch machine bolts (4) and nuts (8), See figure 10.
NOTE - The maximum length of the bolt is 1-1/2 inches.
1 - Lie the furnace on its back and drill a 5/16 inch diame-
ter hole in each corner of the furnace's bottom. See fig-
ure 10 for the correct location of the holes, Drill through
the bottom panel and the bottom flange of the cabinet,
2 - Install one bolt and two nuts into each hole. Screw the
first nut onto a bolt and then insert the bolt into a hole, A
fiat washer may be added between the nut and the bot-
tom of the unit,
3 - Screw another nut onto the bolt on the inside of the fur-
nace base. A flat washer may be added between the
nut and the bottom of the unit,
4 - Adjust the outside nut to the appropriate height and
tighten the inside nut to secure the arrangement,
Leveling Bolt Installation
Inches (mm)
3/8
(10)_r
Furnace Front _'1 [
3/8 1-3/4
(44)
1-3/4
(44)
Leveling Bolt
Locati_
3/8
(10)
I-3/4 (44)
Furnace
Bottom
Leveling Bolt
Locations
3/8
(10)
1-3/4
(44)
FIGURE 10
Horizontal Applications
The G50UH(X) furnace can be installed in horizontal ap-
plications,
Allow for clearances to combustible materials as indicated
on the unit nameplate, Minimum clearances for closet or al-
cove installations are shown in figure 11,
Horizontal Application
Installation Clearances
Top
Left End
Right End
Vent Connector
Type
Top
*Front
Back
Ends
Vent
Floor
Bottom
Type C
0
3 in. (76 ram)
0
2 in. (51 ram)
6 in. (152 ram)
o:_
Type B1
0
3 in. (76 ram)
0
2 in. (51 ram)
1 in. (25 ram)
o:_
*Front clearance in alcove installation must be 24 in. (610 ram).
Maintain a minimum of 24 in. (610 ram) for front service access.
_:For installations on a combustible floor, do not install the furnace
directly on carpeting, tile or other combustible materials other
than wood flooring.
FIGURE 11