NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
Figure 14
Note: Supply wires may be alternatively connected to the outlet using the screw terminals, however
the black supply wire must be wired to a terminal that is opposite (across the outlet) the point where
the white supply wire is connected.
Figure 15
Figure 16
Locate the actuator arm along the right side of
the appliance firebox opening and refer to
Fig-
ure 16
. After completing the installation of the
Outside Combustion Air Kit remove and discard
the actuator arm locking screw.
To operate, push the end of the actuator to the
left as shown in
Figure 16
, until it "pops" free
of its "locked" position. Pull the actuator
forward to open the combustion air door, and
push it back to close. To "lock" the combustion
air door closed, ensure the actuator is pushed
all the way back then push the end of the
actuators to the right until the step in the
actuator moves behind the appliance front
face within the slotted opening.
³₈" Nipple
Gas Stub
¹₂" x ³₈" Flare
Shut-Off Valve
³₈" Flex Tubing
³₈" NPT Flare
Fitting (Remove
Before Hard
Piping)
³₈" Union
³₈" Close Nipple
³₈" Shut-Off Valve
¹₂" x ³₈" Reducer
Gas Valve
(Millivolt or
Electronic)
Gas Flex Line (provided)
Alternate “Hard Piping”
(may be required in some areas, consult local codes.)
Note: ¹₂" NPT At Inlet Of Gas Valve For Electronic Models.
Remove Locking Screw
and “Pop” Actuator to the
Left Before Initial Use
Outside Air
Actuator
Pull Forward to Open,
Push Back to Close
WARNING: DO NOT REMOVE THE AC-
TUATOR ARM LOCKING SCREW UNLESS
THE COMPLETE OUTSIDE AIR VENT SYS-
TEM HAS BEEN INSTALLED IN ACCOR-
DANCE WITH THE DETAILED INSTRUC-
TIONS PROVIDED WITH THE KIT.
White
(Supply)
Black
(Supply)
Bipolar
Terminal
Screw
120 Vac
60 Hz
Green Wire Ground
Connection
Red
(Supply)
120 Vac
60 Hz
120 Vac
60 Hz
Step 7. Installing Outside Air Kit – These
appliances are equipped with an outside (make-
up) air door and integral actuator arm. If the
appliance is to be installed with an outside air
vent system, use only Lennox Models FAOK-4
or FAOK-4LD Combustion Air Kits.
After completing the installation of the optional
combustion air vent system the actuator arm
must be put in service and tested to ensure
proper operation before completing any enclo-
sure around the firebox. Failure to do so may
result in extensive and costly rework.