Lennox Hearth ELDV-40PM Indoor Fireplace User Manual


 
20
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
See Table 9 as an aid in venting component selection
for a particular range of exterior wall thicknesses.
HORIZONTAL VENT FIGURES/TABLES
Notes:
  components (rigid vent pipe and terminal) are shown
in the Figures;  components (flexible vent pipe and
terminal) may also be used.
 Two 45 degree elbows may be used in place of one 90 degree elbow.
The same rise to run ratios, as shown in the venting Figures for 90
elbows, must be followed if 45 degree elbows are used.
 SV4.5VF (Secure Vent), SF4.5VF (Secure Flex) firestop/spacer must be
used anytime vent pipe passes through a combustible floor or ceiling.
SV4.5HF (Secure Vent), SF4.5HF (Secure Flex) firestop/spacer must
be used anytime vent pipe passes through a combustible wall.
 
in a straight (no dips) and recommended to be in a slightly elevated
plane, in a direction away from the fireplace of 1/4" rise per foot (20
mm per meter) which is ideal, though rise per foot run ratios that are
smaller are acceptable all the way down to at or near level.
 The tables show a 1(V) to 5(H) ratio up to a maximum horizontal run
of 20 feet.
 
Use Table 9 as an aid in venting component selection for a particular
range of exterior wall thicknesses.
Figure 31 - Top Vent - ONE 90 DEGREE ELBOW -
ELBOW CONNECTION NOT DIRECTLY AT APPLIANCE
Typical termination shown.
Venting Components Required for Various Exterior Wall Thick-
nesses, when using Typical Termination Kits
Vent Components Required Exterior Wall Thickness - inches (mm)
Termination Kit Only 6 to 9-1/4 (152 to 235)
Termination Kit and 6 In. Vent
Section (SV4.5L6)
10-3/4 to 14 (273 to 356)
Termination Kit and 12 in.
Vent Section (SV4.5L12)
16-3/4 to 20 (426 to 508)
Termination Kit and Tele-
scopic Section (SV4.5L12)
11-3/4 to 20 (299 to 508)
Table 9
Note: See Figure 30 showing wall thickness range
when using SV4.5HT-2 termination kit.
ELBATC
muminiMVmumixaMH
teef)m(teef)m(
*)106.0(4/13)199.0(
3)419.0(7)431.2(
4)22.1(2/101)2.3(
5)425.1(41)762.4(
6)927.1(2/171)33.5(
7)431.2(02)2.6(
.xaM)m4.21(teef04=H+V
.xaM)m2.6(teef02=H
H
V
v
u
When using Secure Flex,
use Firestop/Spacer
SF4.5VF.
u
Ceiling
Firestop/Spacer
(SV4.5VF)
v
When using Secure Flex,
use Firestop/Spacer
SF4.5HF.
Wall Firestop/Spacer
(SV4.5HF)
Min. One
Foot Vent
Section
Required
Example: If 20 feet of (H) hori-
zontal vent run is needed, then
4 feet minimum of (V) vertical
vent will be required.
This table shows a 1(V) to
5(H) ratio. For every 1 foot of
vertical, you are allowed 5 feet
of (H) horizontal run up to a
maximum (H) horizontal run
of 20 feet.
WARNING
Under no circumstances, may separate sections of
concentric flexible vent pipe be joined together.