Lennox Hearth ELDV-40PM Indoor Fireplace User Manual


 
12
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Step 3. INSTALL THE VENT SYSTEM
General Information
These instructions should be used as a
guideline and do not supersede local codes
in any way. Install venting according to local
codes, these instructions, the current National
Fuel Gas Code (ANSI-Z223.1) in the USA or
the current standards of CAN/CSA-B149.1
in Canada.
Ensure clearances are in accordance with
local installation codes and the requirements
of the gas supplier.
Dégagement conforme aux codes d'installation
locaux et aux exigences du foumisseunde
gaz.
Use only approved venting components.
See Approved Vent Components on
Page 2.
These fireplaces must be vented directly
to the outside.
Figure 16
Select Venting System - Horizontal or Vertical
With the appliance secured in framing, de-
termine vent routing and identify the exterior
termination location. The following sections
describe vertical (roof) and horizontal (exterior
wall) vent applications. Refer to the section
relating to your installation. A list of approved
venting components are shown on Pages 36
and 37.
Exhaust Vent
Fixed
Restrictor
Second
Restrictor
The vent system may not service multiple
appliances, and must never be connected to a
flue serving a solid fuel burning appliance. The
vent pipe is tested to be run inside an enclosed
wall (such as a chase). There is no requirement
for inspection openings in the enclosing wall at
any of the joints in the vent pipe.
Installation of Vent Restrictor
A vent restrictor may be needed with this
appliance. The restrictor is installed in the
appliance top flue outlet as shown in Figure
16, either before adding vent, from above, or
after installation of vent from below, within the
firebox. The restrictor is self securing through
a positive friction fit.
Determine the venting for the appliance. If the
vent run will include at least 8 feet of vertical
rise, then install the restrictor in the appliance
collar before connecting any vent (Refer to
Figure 16). Place the second restrictor inside
the fixed restrictor.
Note: The restrictor is included within the
firebox.