KMC BAC-10000 Thermostat User Manual


 
BAC-10000 Series 21 Operation Guide, Rev. J
+B
–A
IN4
IN3
GND
IN2
Common/–/C
Phase/ /R
Analog 9
GND 7–9
Analog 8
Analog 7
Relay 6
SC 4–6
Relay 5
Relay 4
Relay 3
SC 1–3
Relay 2
Relay 1
Outputs
NOTE: Values Shown Are Approximate!
BACnet
MS/TP
Network
Inputs
24 VAC
NOTE: SC = Switched (Relay) Common, Should
Have the Phase Side of 24 VAC Connected
(Wiring Inputs
and Outputs
Dependent on
Application)
24 VAC
}
}
10K Ohms (Thermistor)
or
O Ohms (Closed Contact)
0.1–0.2 VDC (If Network
Token Passing is Present)
}
24 VAC
(Jumper to
Turn Device
On Manually)
NOTE: BAC-1xxx63 Backplate Terminals Shown
with FlexStat Removed; Outputs and Inputs
Vary According to Application
Resistance
Dependent
on Device
Terminal Voltages and Resistances with FlexStat REMOVED from Backplate
If the rmware has just been upgraded, rm-
ware for the wrong model type may have been
installed (e.g., BAC-1xx63 rmware accidentally
installed in a model BAC-1xx36). In the About
menu, ASV may simply read “CUSTOM” instead
of something like “BAC_1xx36 R1.1.0.5” as it
normally would have done. If so, repeat the rm-
ware upgrade and ensure that the correct type of
rmware is selected for the connected model.
NOTE: ASV in the About menu will also show
CUSTOM if any built-in Control Basic
program (1–5) is not running or has auto-
run disabled.
Relay (External) Does Not Work
See Analog Output Does Not Work on page 20.
See Relay (Internal) Does Not Work on page 20
Wiring Issues
CAUTION
Do not mistakenly connect 24 VAC to an analog
output ground. This is not the same as a relay’s
switched common. See the backplate’s terminal
label for the correct terminal.
CAUTION
Relays are for Class-2 voltages (24 VAC) only.
Do not connect line voltage to the relays!
Remove the FlexStat from the backplate and
inspect the terminals for loose or shorted wires.
Use a voltmeter and ohmmeter to check the
terminals for expected values. See the illustration
below and the the Connections and Wiring sec-
tion of the relevant BAC-10000 Series Installation
Guide.
NOTE: Voltage on the BACnet MS/TP terminals
changes according to the signals (passing
of the token) between controllers on the
network. No voltage indicates a bad
connection or simply no active network.
Check the wiring at the connected devices.