KMC BAC-10000 Thermostat User Manual


 
BAC-10000 Series 11 Operation Guide, Rev. J
Date/Time
DATE/TIME
DATE:
TIME: 1:43:59 PM
APR 11 2009
To enter date and time information (only), press:
1. Up/Down to move among entries.
2. Enter to select.
3. Right/Le to move among value elds.
4. Up/Down to increment/decrement value.
More options (such as UTC oset and daylight sav-
ing time options) are available in the (Advanced)
Date/Time menu (see page 7).
Alarms
SAT 4/11 3:20 PM
COOL:
OCC:
FAN:
SERVICE HUM: 20%RH
ALARMS
* SPACE TEMP ALARM 04/11
04/11/09 08:37:56
<AI1> SPACETEMP
PRESENT VALUE = 90.1
EXCEEDS HIGH_LIMIT
<EE1>
SPACETEMPALARM
DELETE ALARM?
NO
YES
A ashing “SERVICE” on the Home screen indicates
an alarm. To view and delete alarms, press:
1. Right to move among elds.
2. Enter to select. (Enter on Alarm Details screen to
delete the alarm.)
3. Le to go back one page.
Built-in alarms are triggered under these conditions:
Space Temp Alarm—temperature outside the
range of 56 to 86° F for over 300 seconds.
Space Humidity Alarm—humidity above 65%
for over 300 seconds. This is available only in
FlexStat models with a humidity sensor and a
dehumidication option selected in the Humid-
ity setup). See Humidity Setup on page 5.
Fan Fail Alarm—no fan status signal within ve
seconds of call for fan (and Input 2 is congured
for the fan status sensor option). See Sensor Setup
on page 6.
Low Limit Alarm (freeze stat)—space
temperature is below the adjustable (under
Damper Setup) low limit alarm temp for one
second (when congured for the economizer
option). Aer a low limit alarm is generated,
the fan will not run until aer the FlexStat
is restarted. See Restart under Reseing the
FlexStat on page 14. See also Damper Setup on
page 5.
(Up to six additional alarms may be added with
custom programming.)
NOTE: Time delays and limits can be modied in
the corresponding Event Enrollment objects
using TotalControl.