KMC BAC-10000 Thermostat User Manual


 
BAC-10000 Series 17 Operation Guide, Rev. J
Troubleshooting
Alarm Issues
Alarm, (False) Fan Fail
Check conguration. Be sure the Fan Status
option is not selected when there is no sensor/
switch for it.
Check that the IN2 (fan status) input pull-up
resistor switches are fully latched in the correct
positions. Any passive, dry contact should use
the 10K Ohm seing. (See the Connections and
Wiring section of the relevant BAC-10000 Series
Installation Guide.)
Check IN2 (fan status) input wiring.
Check the connected fan status sensor/switch.
Using BACstage or TotalControl, check that AI2
(fan status) is not congured as “Out Of Service.”
Alarm, (False) Low Limit (Freeze Stat)
Check the Low Limit Alarm seing—see Damper
Setup on page 5.
Check conguration. Be sure the Economizer
option is not selected when there is no mixed air
temperature sensor.
Check that the IN3 (mixed air temp.) input
pull-up resistor switches are fully latched in the
correct positions (see the Connections and Wiring
section of the relevant BAC-10000 Series Installa-
tion Guide).
Check IN3 (mixed air temperature) input wiring.
Check the connected mixed air temperature sensor.
Using BACstage or TotalControl, check that AI3
(mixed air temp.) is not congured as “Out Of
Service.”
NOTE: Aer a low limit alarm is generated, the
fan will not run until aer the FlexStat
is restarted. See Reseing the FlexStat on
page 14.)
Alarm, (False) Space Temp. or Humidity
See Alarms on page 11.
See Temperature Reading Is Incorrect on page 19.
See Temperature Setpoint Is Not Maintained on
page 19.
Using TotalControl, adjust the limits or time
delay.
Communication Issues
Firmware Upgrade Fails
Ensure the WD (watch dog) jumper is temporar-
ily removed during the upgrade process (see the
KMD-5699 Installation Guide, P/N 913-019-04).
Reinstall the pin on the le and center pins aer
the upgrade process is complete.
Check connections.
Ensure rmware for the correct model is selected
in the Firmware Upgrade Tool.
NOTE: If rmware for a wrong model is acciden-
tally installed, the outputs will not match the
applications/conguration on the display.
NOTE: Backing up the existing seings and
rmware image before or during the
upgrade process is good practice.
NOTE: Restoring to the factory defaults and
reconguring might be needed if how the
FlexStat operates changes. Read all notes
accompanying the rmware update!
KMD-5576 Communication Faulty
Upgrade to the latest version of BACstage (ver.
2.4.0.25 or later required).
Check the seings for the USB port on the
computer (Device Manager > Ports) and the
MS/TP port in BACstage (Access > Connection
Parameters).
Reduce the Max Master number down to the
minimum needed for that network—see (Ad-
vanced) BACnet Communications on page 7.
Install latest driver and check latency seings.
See Latency Seings for KMD-5576 Service Bul-
letin (SB0308A) on the KMC web site.
See also MS/TP Network Communication Faulty
below.
MS/TP Network Communication Faulty
Reduce the Max Master number down to the
minimum needed for that network—see (Ad-
vanced) BACnet Communications on page 7.
Check that EOL switches are fully latched in the
correct positions (see the relevant BAC-10000
Series Installation Guide).
Check MAC address and device instance num-
bers.
Check baud rate.