Trouble Shooting Suggestions
Problem Corrective Suggestion
Wall hook/bracket loose or damaged Secure, repair or replace
Nozzle obstructed Clear , clean or replace
Discharge hose assembly worn, cracked Replace
or damaged.
Hose o-ring missing, cracked or damaged Replace and lightly lubricate
Hose retainer/band missing or damaged Replace
Valve discharge port obstructed/dirty Clean or empty and replace
Pull pin bent, corroded, missing or damaged Replace
Lever/handle loose, bent or damaged De-pressurize and replace
Pressure gauge reads outside green area Check ambient temperature
correlation.
De-pressurize and
recharge or replace*
Pressure gauge damaged De-pressurize and replace*
Gauge operating pressure differs from label De-pressurize and replace*
Gauge does not indicate for use with dry chemical De-pressurize and replace*
Gauge does not indicate compatible with De-pressurize and replace*
valve material
Total charge weight of unit outside tolerance De-pressurize and recharge
Nameplate instructions missing or illegible Replace
Agent cylinder damaged or corroded Inspect and hydrostatic re-test or
dispose of in accordance with
NFPA-10
*For gauge replacement, Kidde recommends the use of Loctite - 242 thread sealant be
utilized and allowed to properly cure.