Hunter Fan R410A Air Conditioner User Manual


 
-
6
-
Section Display section
Error code of remote controller
Inspection LED (red) of indoor unit PCB
Inspection LED (red) of outdoor unit PCB
• Displays the error of higher priority (When plural errors are persisting)
• Displays the present errors.
(When a new error has occurred after the former error was reset.)
Error detail Error code Timing of error detection
Wrong connection between the indoor and
outdoor units.
“ Wait ”
Normally, 30 seconds after the power is turned ON.
Normally after the power is turned ON (during communications).
Broken wire of heat exchanger thermistor
Drain error (float switch motion)
No communications even once with the outdoor unit.
After 1 or more communications of the indoor unit with the remote controller
following power on, transmission errors cause an interruption for 2 minutes.
After communications with the outdoor unit 1 or more times, communications
are abnormal continuously for 2 minutes.
When an input temperature of –50°C or lower is measured by the return air
thermistor is measured for 5 seconds or longer within 60 minutes after the
first detection.
When an input temperature of –50°C or lower is measured by the heat
exchanger thermistor is measured for 5 seconds or longer within 60 minutes
after the first detection.
Transmission error of remote controller
indoor unit
Transmission error between indoor/outdoor
units
The number of connected indoor units
exceeds the connection limit (when
multiple units are control by a single remote
controller).
Broken wire of indoor unit return air
thermistor
······················
Error detail Error code Timing of error detection
Broken wire of heat exchanger thermister
Broken wire of discharge pipe thermistor
Broken wire of outdoor air temperature
thermistor
Broken wire of power transistor
thermistor
When a thermistor input temperature of –30°C or lower is measured for 5
seconds or longer 3 times within 40 (60) minutes after the 1st detection
between 2 minutes and 2 minutes 20 seconds after compressor operation
starts.
When a thermistor input temperature of –30°C or lower is measured for 5
seconds or longer 3 times within 40 (60) minutes after the 1st detection
between 2 minutes and 2 minutes 20 seconds after compressor operation
starts.
When a thermistor input temperature of –10°C or lower is measured for 5
seconds or longer 3 times within 40 (60) minutes after the 1st detection
between 10 minutes and 10 minutes 20 seconds (between 2 minutes and 2
minutes 20 seconds) after compressor operation starts.
When the under-dome thermistor input temperature of –10°C is measured for
5 seconds or longer 3 times within 40 minutes after the 1st detection between
10 minutes and 10 minutes 20 seconds after compressor operation starts.
(b) Display sequence of error, inspection display lamp
1) One kind error
Display corresponding to the error is shown.
2) More than one errors.
3) Timing of error detection
Indoor unit side.
Notes (1) Values in ( ) show for the FDCA301~601 models.
(2) The power transistor temperature sensor is used in the FDCVA151~251 models only.
Outdoor unit side.