Hunter Fan R410A Air Conditioner User Manual


 
-
11
-
CNT
CNV
CNO
CNH
CNF
CNB
CNQ
CNN1
CNN2
SW2 SW10
SW5 SW7
SW9SW8
CNZ CNI
CNO
CNA
F3
F2
CNK2CNK1
CNW2
CNG
CNE
CNW0
CNW1
CNM3
52X3
52X5 52X4
52X2 52X1 52X6
L3L2
L1
L4
CNJ2 CNR
F1
LED1
LED2
PCB power supply connector
(Primary side)
PCB power supply connector
(Secondary side)
Heat exchanger thermistor
(Thl-R2)
Address swith
(SW2)
DIP switch
(SW5)
DIP switch
(SW9)
J6
(SW8)
J1~J4
(SW7)
Float switch
J10~J11
(SW10)
Connector
(CNT)
Drain motor
Remote controller
Power supply
Heat exchanger thermistor,
Return air thermistor
(Thl-R1, Thl-A)
Input signal - Reverse invalid
Input signal - Rus stop
Heating thermostat OFF-Lo
Heating thermostat OFF-Stop, Lo
Normal operation operable
Operation permission prohibited
Normal
Heating temp. +3
Freeze prevention fan control activated
Freeze prevention fan control deactivated
J1 (SW7-1)
J2 (SW7-2)
J3 (SW7-3)
J4 (SW7-4)
J6 (SW8-2)
With
None
(1)
With
None
(1)
With
None
(1)
With
None
(1)
With
None
(1)
Name Function
Note (1)
(2)
None means that jumper wire is not provided on the PCB or the
connection is cut
The replacement board is not equipped with jumpers J1 ~ J4, J6.
Instead, SW7 and 8, with the same functions as jumpers J1~J4, J6, are
used in the position where the jumpers were previously. Set SW7 and 8
locally in accordance with the above table.
Setting time : 1000hrs. (Unit stop)
Setting time : 1000hrs. (Display)
Setting time : 600hrs. (Display)
Setting time : 180hrs. (when shipped from factory)
SW5-4SW5-3
ON
OFF
ON
OFF
ON
OFF
Switch Function
Emergency operation
Normal
Fan control : High speed (High Ceiling)
Fan control : Standard
SW9-3
SW9-4
Switch Function
Remote controller air flow
Remote controller air flow 1 speed
Remote controller air flow 2 speed
Remote controller air flow 3 speed
OFF
ON
OFF
ON
ON
OFF
ON
OFF
Switch Function
OFF
ON
SW10-3
(J11)
SW10-2
(J10)
Control change switch (SW5, SW9, SW10)
Function of DIP switch SW5 (Usually all turned OFF)
Function of DIP switch SW9 (Usually all turned OFF)
Change by the jumper wire
Function of DIP switch SW10 (Usually all turned OFF)
Model: FDUR series