Honeywell TB7100A1000 Thermostat User Manual


 
TB7100A1000 MULTIPRO™ MULTISPEED AND MULTIPURPOSE THERMOSTAT
62-0273—05 12
NOTE: Press the Done key to exit the Installer System Test.
0700 Temperature
Display Offset
0 -3 (-1.5)— -3°F (-1.5°C)
-2 (-1.0)— -2°F (-1.0°C)
-1 (-0.5)— -1°F (-0.5°C)
0 (0.0)—0°F (0.0°C)
1 (0.5)—1°F (0.5°C)
2 (1.0)— 2°F (1.0°C)
3 (1.5)—3°F (1.5°C)
This offset applies to both the control temperature
and to the display temperature for indoor sensor
(and remote indoor sensor).
0710 Restore Factory
Defaults
0 0—No
1—Yes
Resets all ISU parameters to default values and
resets the schedule to default energy savings (see
Table 5). Retains only calendar settings and time.
0720 Screen Display 2 0—Display Room
Temperature
1—Display Setpoint
2—Display Both
INSTALLER TESTS
Test 1 Installer Test
Cool
00Off
1—Cool Stage 1
Only shown if system has cool stages.
Test 2 Installer Test
Fan
00Off
1—Fan Stage 1
2—Fan Stage 2
3—Fan Stage 3
Only shown if system has fan.
Test 3 Installer Test
Heat
00Off
1—Heat Stage 1
2—Heat Stage 2
Only shown if system has fan.
Systems with 2 Heat stages will have option 2
enabled for Installer Test 3.
Test 4 Installer Test EM
Heat
0 0—EM Heat Off
1—EM Heat On
Only shown if multi-stage HP is selected (heat
pump with more heating than cooling stages).
Table 4. Installer Setup Menu. (Continued)
Installer
Setup
Number
Installer Setup
Name
Default
Setting All Settings Notes