Honeywell TB7100A1000 Thermostat User Manual


 
TB7100A1000 MULTIPRO™ MULTISPEED AND MULTIPURPOSE THERMOSTAT
62-0273—05 10
0300 Changeover 1 0—Manual
1—Auto
Only shown if system has both heat and cool
stages (ISU 0170). Shown for CNV, HP, PTAC and
4 pipe fan coil (ISU 0170). Not shown for 2 pipe
fan coil modes.
0310 Deadband 3°F
(2°C)
2 (1.5)—2°F (1.5°C)
3 (2.0)—3°F (2.0°C)
4 (2.5)—4°F (2.5°C)
5 (3.0)—5°F (3.0°C)
6 (3.5)—6°F (3.5°C)
7 (4.0)—7°F (4.0°C)
8 (4.5)—8°F (4.5°C)
9 (5.0)—9°F (5.0°C)
Only shown if Automatic Changeover selected
(ISU 0300).
0320 Temperature
Indication Scale
0 0—°F
1—°C
0330 Daylight Saving 1 0—Disabled
1—Enabled (US)
0340 Remote Temp
Sensor/Remote
Setback/
Changeover Input
0 0—None
1—Remote 10K Indoor
2—Remote 20K Indoor
3—Changeover 2 pipe
Fan Coil modes only
4—Changeover 2 pipe
Fan Coil modes only
Only shown on models that offer remote sensing.
NO input (default mode is Heat)
NO input (default mode is Cool)
0340
(Non-
program
mable)
Remote Temp
Sensor/Remote
Setback/
Changeover Input
0 0—None
1—Remote 10K Indoor
2—Remote 20K Indoor
3—Changeover 2 pipe
Fan Coil modes only
4—Changeover 2 pipe
Fan Coil modes only
5—Remote Setback
6—Remote Setback
Only shown on models that offer remote sensing.
NO input (default mode is Heat)
NO input (default mode is Cool)
Hotel card NO, with 1 second software delay going
from UnOcc to Occupied; 2 minute delay going
from Occupied to UnOcc.
Hotel Card NC, with 1 second software delay
going from UnOcc to Occupied; 2 minute delay
going from Occupied to UnOcc.
0341 Delay for Remote
Setback
0 0—No Delay
2—2 Minute Delay
Only shown if Remote Setback (ISU 0340) is
enabled.
0342 Override Option
(only available in
non-programmable
mode)
0 0—No Override
1—Override
This option is only available for non-programmable
mode (ISU 0160)
0343 Unoccupied
Heating Setpoint
(only when remote
setback enabled)
60°F 50-65°F
10-18°C
0346 Unoccupied
Cooling Setpoint
(only when remote
setback is enabled)
80°F 75-90°F
24-30°C
0347 Fan Ramping 1 0—Disabled (Lo, Med, Hi)
1—Enabled
To enable the fan ramping algorithm. Only
available for fan coil or PTAC applications.
0348 Fan Mode 0 0—User can choose
Cycle or Constant 3
speed: Low->Med->
High->Aut o-> Low
1—Cycle Only - Auto only
To select a particular fan mode: Auto is the fan
ramp mode. If ramping is not selected, fan mode
automatically defaults to Low Med High (Constant
only) and ISU 0348 is unavailable. Only available
for fan coil or PTAC applications.
Table 4. Installer Setup Menu. (Continued)
Installer
Setup
Number
Installer Setup
Name
Default
Setting All Settings Notes