Honeywell PDX65S65F(B,S,C)*(N,X) Water Heater User Manual


 
Sequence of Operation
3. Pressure Switch/Blower Temperature Fault:
a) Pressure switch closed at start of call for heat - The control waits four seconds then, proceeds to flash
2 times with 3 second pause. The control waits 2 minutes and then turns on blower for 30 seconds. The blower
turns off after 30 seconds and the control waits for pressure switch to open. Any time the Pressure switch opens,
the blower turns on (or stays on) and the control proceeds to waiting for pressure switch to close.
b) Pressure switch or blower temperature switch failed open - The control runs the blower for 30 seconds
waiting for the pressure switch and/or blower temperature switch to close. If either switch does not close in 30
seconds, the blower turns off and the control flashes 3 times with 3 second pause. The control waits two
minutes before turning on the blower for another 30 seconds to see the circuit close. This cycle repeats as long as
there is a call for heat or until the circuit closes.
c) Pressure switch or blower temperature switch opens during burner operation - The control turns off the
pilot and main valve, runs blower for 15 seconds (inter-purge) waiting for pressure switch and/or blower
temperature switch to close. If either switch fails to close, the control proceeds as described in 3b above. If the
circuit closes again by the end of the inter-purge, the recycle counter is incremented, if the recycle count has
not reached its limit (4), another trial for ignition
be
gins. If the recycle count has been reached, the control
turns off the blower and flashes 6 times then 2 times with 3 second pause. The control waits 5 minutes before
repeating ignition sequence.
4. Trial For Ignition Fault:
a) Pressure switch opens during trial - The control turns off igniter and pilot valve. The gas control proceeds
as described in 3b above. If the pressure switch closes within 30 seconds the gas control will continue with trial for
ignition starting at blower pre-purge.
b) Flame Not Sensed - The control energizes the spark igniter attempting to light the pilot and prove flame. If
flame is not sensed within 90 seconds, the igniter turns off, the pilot valve is closed and the gas control runs the
blower through post purge and flashes 6 times then once with 3 second pause. The control waits 5 minutes before
repeating the ignition sequence.
5. Flame Sensing Fault:
a) Flame lost during run - The control turns off pilot and main valves, runs blower for 15 seconds (inter purge).
The control increments the recycle count, if the recycle count has not reached its limit (4), another trial for
ignition begins. If the recycle count has been reached, the control turns off the blower and flashes 6 times
then 3 times with 3 second pause. The control waits 5 minutes before repeating the ignition sequence.
b) Flame sensed out of sequence - the control only looks for pilot flame when the blower is running. If flame is
present when the pilot valve is not open, the control proceeds to wait for flame loss and flashes 5 times with 3
second pause. This continues until flame is lost, once the flame signal is lost, the control flashes 6 times then 4
times with 3 second pause. The control waits 5 minutes before repeating the ignition sequence.
Page 12
PDX Series
12