Honeywell IAQ Thermostat User Manual


 
VisionPRO® IAQ
5 69-1816EFS—03
**See page 6
0502 Furnace filter
alert options
0 Timer counts Heat & Cool run time
1 Timer counts Cool run time only
0510 Humidifier pad
change alert *
E Auto Discover **
0 Off
1 90 calendar days or 30 days run time
2 180 calendar days or 60 days run time
3 365 calendar days or 90 days run time
0520 UV lamp change
alert
E Auto Discover **
0 Off
1 365 calendar days (1 year)
2 730 calendar days (2 years)
0530 Adaptive Intelligent
Recovery™
1 On **
0 Off
0540 Program periods
4 4 program periods (Wake, Leave, Return, Sleep)
2 2 program periods (Wake, Sleep)
0580 Compressor off
time (min.)
5 5 minute compressor off time **
[Other options: 0 to 4 minutes]
0600 Heat temperature
range stop
90 Max. heat temperature setting is 90°F (32°C)
[Other options: 40 to 90°F (4°C to 32°C)]
0610 Cool temperature
range stop
60 Min. cool temperature setting is 60°F (15°C)
[Other options: 60-99°F (15°C to 37°C)]
0640 Clock format
12 12-hour time (i.e., "3:30 pm")
24 24-hour time (i.e., "15:30")
0650 Extended fan
timer (heat)
0 Off
[Other options: Fan runs for 30, 60, 90 or 120 seconds after call for
heating ends]
0660 Extended fan
timer (cool)
0 Off
[Other options: Fan runs for 30, 60, 90 or 120 seconds after call for
cooling ends]
0670 Keypad lock
0 Keypad unlocked (fully functional)
1 Partially locked (access to temperature settings only)
2 Fully locked
0680 Heat temperature
control
2 Standard temperature control (recommended)
1 Choose if room is warmer than set temperature
3 Choose if room does not reach set temperature
0690 Cool temperature
control
2 Standard temperature control (recommended)
1 Choose if room is cooler than set temperature
3 Choose if room does not reach set temperature
0700 Temperature
display offset
0 Thermostat displays actual room temperature
[Other options: -3°F to +3°F offset (-1.5°C to 1.5°C)]
0701 Humidity
display offset
0 Thermostat displays actual room humidity
[Other options: -5% to +5% offset]
0710 RESET
0 No reset
1 Reset installer options & program schedule to factory default (only
date and time settings are retained)
Setup function Settings & options (factory default in bold)
Installer setup
* Humidifier Pad replacement will be displayed in the user interface as run
time days if ISU 372 is set to 1 or 3 and calendar days if ISU 372 is set to 0.