Honeywell IAQ Thermostat User Manual


 
VisionPRO® IAQ
3 69-1816EFS—03
0210 External fossil
fuel kit
1 External fossil fuel kit controls backup heat
0 Thermostat controls backup heat (outdoor sensor required)
0220 Stage 1 compressor
1cycle rate
E Auto Discover **
[Other options: 1 to CPH]
0230 Stage 2 compressor
cycle rate
E Auto Discover **
[Other options: 1 to 6 CPH]
0240 Stage 1 heat cycle
rate (CPH= cycles
per hour)
E Auto Discover **
[Other options: 1 to 12 CPH]
0250 Stage 2 stage heat
cycle rate (CPH)
E Auto Discover **
[Other options: 1 to 12 CPH]
0260 Stage 3 heat cycle
rate (CPH)
E Auto Discover **
[Other options: 1 to 12 CPH]
0280 Backlight 0 Backlight on for approx. 45 seconds after keypress
1 Backlight always on low intensity, full bright after keypress
0300 Manual/Auto
changeover
0 Manual (User options: Heat/Cool/Off)
1 Automatic (User options: Heat/Cool/Auto/Off)
(System selects heat/cool based on indoor temp.)
0310 Auto changeover
deadband
3 Heat/cool settings 3°F apart (1.5°C)
[Other options: 2-9 (2°F to 9°F/1°C to 5°C)]
0320 Temperature display 0 Fahrenheit
1 Celsius
0330 Daylight savings
2 Auto-change to daylight savings time (2007 and beyond, for
areas that use the new 2007 DST calendar)
1 Auto-change to daylight savings time (through 2006, and for areas
that do not use the new 2007 DST calendar)
0 Daylight savings time is turned off
0340 Indoor temp.
sensor
0 Display temp. at thermostat location only
1 Display temp. at indoor sensor location(s)
2 Average between thermostat & sensor location(s)
0342 Outdoor temp.
sensor
E Auto Discover **
0 None
1 Remote sensor
0345 Dual fuel heat
pump control
1 Balance point plus 2°F droop **
0 Balance point only **
2 Balance point/Aux Heat Lockout plus 2°F droop **
0346 Dual fuel heat
pump upstage to
furnace timer
60 60 minutes **
0 Off
[Other options: 30, 45 or 75 minutes]
0350 Heat pump
compressor lockout
0 No compressor lockout **
[Other options: 5 to 60°F (-15°C to 15.5°C)]
0360 Heat pump
auxiliary lockout
0 No heat pump auxiliary lockout **
[Other options: 5 to 65°F (-15°C to 18.5°C)]
0365 Discharge temp.
sensor
E Auto Discover **
0 No
1 Yes
0370 Indoor humidity
sensor
1 Internal sensor in thermostat
0 Sensors disabled
E Auto Discover **
Setup function Settings & options (factory default in bold)
Installer setup
**See page 6